Every item of equipment or enclosure within which a nominal voltage exceeding 230V to earth and where the presence of such voltage would not normally be expected, shall be arranged that before access is gained to a live part, a warning of the maximum voltage present is clearly visible.
Available for voltage levels 110V, 120V, 208V, 230V, 400V, 415V and 480V
Available for sizes : 30mm x 30mm, 40mm x 40mm and 55mm x 55mm
To purchase this product go to our online store or https://shopee.sg/voltlim
If wiring additions or alterations are made to an installation such that some of the wiring complies with 514.4 but there are also wiring to previous versions of these clauses, a warning notice shall be affixed at or near the appropriate distribution board with the following wording:
CAUTION This installation has both old and new cable colour codes. Great care should be taken before undertaking extension, alteration or repair that all conductors are correctly identified.
To purchase this product go to our online store or https://shopee.sg/voltlim
Where an installation incorporates an RCD a notice shall be fixed in a prominent position at or near the origin of the installation. The notice shall read as follows:
This installation, or part of it, is protected by a device which automatically switches off the supply if an earth fault develops. Test quarterly by pressing the button marked 'T' or 'Test'. The device should switch off the supply and should then be switched on to restore the supply. If the device does not switch off the supply when the button is pressed, seek expert advice.
To purchase this product go to our online store or https://shopee.sg/voltlim
A notice of such durable material as to be likely to remain easily legible throughout the life of the installation shall be fixed in a prominent position at or near the origin of every installation upon completion of the work carried out in accordance with Chapter 61 or 62.
To purchase this product go to our online store or https://shopee.sg/voltlim
Where an installation include alternative or additional source of supply. warning notices shall be affixed at the following locations in the installation.
(i) At the origin of the installation
(II) At the meter position, if remote from the origin
(iii) At the consumer unit or distribution board to which the alternative or additional sources are connected
(iv) At all points of isolation of all sources of supply
The warning notice shall have the following wording:
WARNING - MULTIPLE SUPPLIES Isolate all electrical supplies before carrying out work.
Isolate the mains supply at ….....................................
Isolate the alternative supplies at ….........................
To purchase this product go to our online store or https://shopee.sg/voltlim
Means shall be provided to enable the PV power supply system to be isolated from the public supply system.
Warning notices for dual supply source shall be affixed at the following locations in the installation.
(i) At the origin of the installation
(II) At the meter position, if remote from the origin
(iii) At the consumer unit or distribution board to which the PV power supply system is connected
(iv) At all points of isolation of both sources of supply
To purchase this product go to our online store or https://shopee.sg/voltlim
At the distribution board information shall be provided indicating those circuits having a high protective conductor current. This information shall be positioned so as to be visible to a person who is modifying or extending the circuit.
To purchase this product go to our online store or https://shopee.sg/voltlim
Socket-outlets not protected by RCD e.g for fire alarm, battery chargers, and medical equipment shall be labelled with word in white against a red background.
To purchase this product go to our online store or https://shopee.sg/voltlim
SS 638 Caution Socket-Outlet Not Protected By RCD Sticker Label 60mm x 15mm
To purchase this product go to our online store or https://shopee.sg/voltlim
To purchase this product go to our online store or https://shopee.sg/voltlim
To purchase this product go to our online store or https://shopee.sg/voltlim
To purchase this product go to our online store or https://shopee.sg/voltlim
To purchase this product go to our online store or https://shopee.sg/voltlim
A durable label to SS 322 with words "Safety Electrical Connection - Do Not Remove" shall be permanently fixed in a visible position at or near:
(i) the point of connection of every earthing conductor to an earth electrode, and
(ii) the point of connection of every bonding conductor to an extraneous-conductor-part,
(iii) the main earth terminal, where separate from the main switchgear.
Note: This label shall be treated as an additional warning notice to the metal label which complying with SS 322 requirements.